Parameters for the module
- Diagnostic alarm: On | Off
- Representation values: SIMATIC* S7 | SIMATIC* S5
Parameters for each channel
- Wire break detection: On | Off
- Output range: ±10 V | 0–10 V | 1–5 V
- Substitute value functionality: Outputs de-energized | Retain last value | Apply substitute value
- Substitute value: 16 bit analog value (±27648)
- Output range ±10 V, 0–10 V, 1–5 V
- Resolution 11 bit + sign
- Substitute value functionality
- Diagnostic messages
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- 4 analog outputs, electrically isolated from the backplane bus
- 4 process output words (4 bytes)